FN300 - Thermal Flow Switch with LED Digital Display
  • 4 - digit LEDs
  • Flow velocity / percentage display
  • Wide measuring range
  • Measuring span programmable
  • PNP / NPN programmable
  • 4..20mA/0…20mA/1…5V/0…5V output programmable
  • Rotatable indicator
  • Easy to read, robust display
Applications
  • Hydraulic system
  • Pump protection
  • Cooling system
  • Venting systems
  • Water treatment
  • Leak monitoring
  • Lubrication system
  • Machinery manufacture
  • Equipment manufacture
  • Engineering project
Specifications
Measuring range
    Water 1...200cm/s
    Oil 3…300cm/s
    Air 20…2000cm/s
Applicable medium water, oil and gas which is compatible with 316 stainless steel
Repeatability 1%@<0.6m/s; 3%@<1.5m/s; 10%@>1.5m/s ( for water)
Pressure rating 100 bar (200bar selectable)
Initialization time 1 … 8s
Response time 2s typical
Power supply 24±10%Vdc
No-load current consumption ≤100mA (power supply 24Vdc)
Switching output
    Output Push-pull(compatible with PNP / NPN) NC / NO configurable
    S1,S2 output current <500 mA
    Voltage drop <1V
Current analog output
    Output 3-wire 0...20mA / 4...20mA programmable
    Load RA RA≤0.5Kohm
Voltage analog output
    Output 3-wire 0...5V / 1...5V programmable
    Load RA RA>10Kohm
Wiring Protection Reverse polarity, Overvoltage and Short-circuit
Display
    Design 8mm height, red 4-digit LED
    Display range -1999...9999
Temprature
Operating -40…85℃
Medium -20…85℃, up to130℃(not more than 2 hours)
Materials
    Housing 304 stainless steel
    Probe 304 stainless steel/316 stainless steel(for the sanitary )
Protection class IP67
Electrical connection M12 x 1 plug